VSL-HSPE06 is recommended for use both in open air and on underground power distribution cables with PVC, lead or XLPE sheets. Definitive recovery with the layer of spiral coated hot melt adhesive.
Resistant to fluids, solvents and UV radiation
Shrink ratio: 3:1
Protects power cables up to 1000 V and telecommunication cables
Very easy installation over the cable end
Environment definitive watertight seal
Effectively offering protection against oxidation, ozone, UV-radiation
Optional adhesive liner provides complete environmental protection and insulation
RoHS compliant
Operatingtemperature
Minimum shrinktemperature
Minimum full recoverytemperature
-55°C to +110°C
80°C
120 °C
Standard Color: Black.
Property
Test Method
Typical Data
Physical
Tensile Strength
ASTM D 2671
≥12Mpa
Elongation
ASTM D 2671
≥200%
Heat Shock
ASTM D 26714hrs at 225°C
≥100%
Specific Gravity
ASTM D 792
1.1g/cm3
Electrical
Dielectric Strength
IEC 60243
≥12 kV/mm
Volume Resistivity
IEC 93
≥1014ΩNaN
Chemical
Water Absorption
ISO62
≤0.15%
Size
As Supplied (mm)
After Recovery(mm)
Cable Diameter(mm)
D(Min)
D(Max)
A (±10%)
L (±10%)
D (±5%)
Standard length end caps
12/4
12
4.0
15
40
2.6
4-10
14/5
14
5.0
18
42
2.2
5-12
20/6
20
6.0
25
55
2.5
6-16
25/8.5
25
8.5
30
65
2.5
10-20
35/16
35
16.0
35
83
3.3
17-30
40/15
40
15.0
40
75
3.3
18-32
55/26
55
26.0
50
105
3.5
28-48
75/36
75
36.0
55
115
4.2
45-68
100/52
100
52.0
70
130
4.0
55-90
120/60
120
60.0
70
150
4.2
65-110
145/60
145
60.0
70
150
4.2
70-130
160/82
160
82.0
70
133
4.5
90-150
200/90
200
90.0
70
145
4.5
100-180
Extended length end cap
14/5
14
5.0
30
55
2.2
5-12
45/15
45
15.0
40
110
3.3
18-34
55/24
55
23.0
70
140
3.8
25-48
62/24
62
23.0
70
140
3.8
25-55
75/32
75
32.0
70
150
4.0
40-68
75/36
75
36.0
70
170
4.2
45-68
105/45
105
45.0
65
150
4.0
50-90
Note:Printing, special sizes or colors available on request.